Harrington Signal HS-3100/3200 Fire Alarm Control UnitInstallation ManualRevision 2 January 2009Document # LT-2000HARHARRINGTON FIRE ALARM SIGNAL INC
HS-3100/3200 Installation Manual4Display BoardThe Display Board provides LED and LCD statusannunciation, hotkeys, and keypads for messageretrieval and
HS-3100/3200 Installation Manual5Note: Not to be used for ULC applications.DACT Module - PID HS3DL The optional Digital Alarm Communicator Transmitter
HS-3100/3200 Installation Manual6Testing Circuit SupervisionUse the following procedures in the table below to confirm that SLCs and NACs are supervis
HS-3100/3200 Installation Manual72.0 Technical Specifications2.1 Electrical SpecificationsTable 1: AC InputTable 2: Battery Power (Use sealed lead aci
HS-3100/3200 Installation Manual8Table 3: Addressable Input (Signaling Line Circuit)Table 4: Notification Appliance Circuit Output Circuits: Table 5:
HS-3100/3200 Installation Manual9Table 7: Communications PortsTable 8: Environmental SpecificationsPort RatingRS-232-2 (EVAX) Fixed baud rate 9600 bps
HS-3100/3200 Installation Manual103.0 Installation3.1 Unpacking the HS-3100 or HS-3200The basic HS-3100/HS-3200 package includes the following compone
HS-3100/3200 Installation Manual11Replacing the Outer Door1. Unlock the Door with the key provided.2. Detach the grounding strap (Qty: 2) from the bac
HS-3100/3200 Installation Manual1229"(740 mm)14-1/2" (368 mm)27-1/2"(699 mm)1-1/4"(32 mm)Battery shelf21-3/4"(552 mm)8-1/2&qu
HS-3100/3200 Installation Manual133.3 Internal Assembly• Attach AC wiring to the AC Terminal Block (see Figure 4 on page 16). Attach green ground wire
HS-3100/3200 Installation Manual14Communications harness is routed under HS3CTYB PCB and white plastic from location circled on HS3CTYB to location ci
HS-3100/3200 Installation Manual153.4 WiringPower ConnectionsThe Main Control Unit requires an AC power supply. This supply is connected as shown belo
HS-3100/3200 Installation Manual16The internal batteries are not used when an external battery box is used. The wires for connectingthe power supply b
HS-3100/3200 Installation Manual17Addressable Circuit ConnectionsAddressable Class B (Style 4) CircuitThis is a 2-wire supervised Class B (Style 4) co
HS-3100/3200 Installation Manual18Notification Appliance Circuit ConnectionsClass B (Style Y) NACThis is a 2-wire Class B (Style Y) supervised signali
HS-3100/3200 Installation Manual19EVAX System Wiring 3.5 Maximum Wiring Length for Addressable CircuitsNote: Distances noted in this table account for
HS-3100/3200 Installation Manual204.0 Appendix A: Compatible Addressable DevicesTable 9:System Sensor Compatible Addressable DevicesModel DescriptionT
HS-3100/3200 Installation Manual215.0 Appendix B: Battery Calculations & Compatible Batteries5.1 Battery Calculation Worksheet1. Enter the number
HS-3100/3200 Installation Manual22See next page for battery selection calculations.Notes:* Each relay, when active, will draw 17mA. The alarm current
HS-3100/3200 Installation Manual235.2 Battery Selection Calculations1. From previous calculations, locate total Standby Current (A) and convert to amp
HS-3100/3200 Installation ManualiTable of Contents1.0 Technical Information ...
HS-3100/3200 Installation Manual246.0 Appendix C: Compatible Synchronized Notification AppliancesManufacturerAppliance ModuleCandela# of AppliancesMir
Harrington Signal Inc. 2519 4th AvenueMoline, IL 61265HARRINGTONFIRE ALARMSIGNAL INC.
HS-3100/3200 Installation ManualiiiList of Tables & FiguresTable 1: AC Input ...
HS-3100/3200 Installation Manual11.0 Technical Information1.1 IntroductionThe HS-3100/3200 Fire Alarm Control Panel (FACP) is the heart of a sophistic
HS-3100/3200 Installation Manual21.4 Applications & ServicesThis fire alarm control panel is listed for use in the following applications:• Local
HS-3100/3200 Installation Manual31.7 System ComponentsBasic SystemA basic system consists of the Back Box, Main Board,Display Board and one transforme