© Apollo Fire Detector Ltd 2004
Harrington Signal Inc., 2519 4th Avenue, Moline, Illinois 61265, USA
Tel: 800 577 5758 Fax: 309 762 8215
Website: www.harringtonfi re.com
4
1
I-Spy Mini Switch Monitor Module and
I-Spy Mini Priority Switch Monitor Module
Installation Instructions
General
The I-Spy Mini Switch Monitor Module, part no IS816, is a loop-powered device, which
incorporates a monitored input circuit for connection to switches. The module is supplied as
a small plastic housing designed to fit into an electrical box. Six flying leads of 18AWG are
used to connect the module.
A red LED flashes in synchronization with the current pulse reply from the device. If output
bit 2 is set the LED is illuminated continuously.
The I-Spy Mini Priority Switch Monitor Module, part no IS815, has, in additon, a priority
interrupt facility to give fast response and can be fitted in an electrical box behind a pull
station.
Note: the I-Spy Mini Switch Monitor Module and the Mini Priority Switch Monitor Module are
not designed for outdoor use unless they are mounted in a suitable weatherproof enclosure.
Installation
1. The I-Spy Mini Switch Monitor Module and the I-Spy Mini Priority Switch Monitor Module
are not physically attached to the electrical box other than by means of the flying leads.
2. Connect the modules for Class A wiring or Class B wiring (Fig 2). Bit 8 of the DIL
switch is used to select the class of wiring. All wiring must conform to local codes and
regulations.
39214-239/Issue 2
Functional Test Data
OUTPUT BIT FUNCTION INPUT BIT FUNCTION
2 ALARM LED 2 ALARM LED CONFIRMATION
1 = ON 1 = ON
0 = OFF 0 = OFF
1 REMOTE TEST 1 INDICATES WIRING CLASS
1 = TEST ENABLED 1 = CLASS B*
0 = NORMAL 0 = CLASS A
0 NOT USED 0 ALARM STATUS
1 = ALARM
0 = NORMAL
* Note: Toggles to ‘0’ in alarm.
Technical Data
Monitored circuit
Current consumption
Quiescent 600µA
Alarm (LED on) 4.6mA
End-of-line supervisory resistance 47kΩ, 0.5W
Analog levels
Open-circuit fault 4
Normal 16
Alarm on switch closure 64
Compatibility Information
The I-Spy Mini Switch Monitor and I-Spy Mini Priority Switch Monitor modules have been
approved by Underwriters Laboratories Inc. for use with the Fire Spy
Tracker 8000 control
panel.
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - Installation Instructions

© Apollo Fire Detector Ltd 2004Harrington Signal Inc., 2519 4th Avenue, Moline, Illinois 61265, USATel: 800 577 5758 Fax: 309 762 8215Website: www.h

Pagina 2 - Fig 3. DIL Switch

23Address SettingSegments 1–7 of the DIL switch are used to select the address of the module. Each of the seven segments must be set to ‘0’ (ON) or ‘1

Comentarios a estos manuales

Sin comentarios